Constant Pressure Pump Controller: How To Choose A W713 For Your Water System
A constant pressure pump controller adjusts pump speed in response to a pressure signal, helping maintain a target pressure as water demand changes. The right controller must match the available power supply, motor voltage and current, pressure sensor, and the number of pumps in the system.
Liyuan’s 2026 catalog lists the W713 pump controller with constant-pressure control, multi-pump linkage and 220 V or 380 V supply configurations. The exact input and output depend on the model—not every W713 works with every pump.
What Problem Does A Constant Pressure Pump Controller Solve?
Consider a water supply system serving a workshop during the day and only a few taps at night. The required flow changes, but users still need suitable pressure.
A pressure switch normally cycles a fixed-speed pump between two pressure settings. A variable-speed pump controller instead adjusts motor speed while the pump runs, using pressure feedback to maintain a target within the system’s capability.
The benefit depends on the actual installation. If the pump cannot deliver the required flow at the required head, or the well cannot supply enough water, a controller cannot create the missing capacity.
Design a constant pressure system around both the highest demand and the lowest expected demand—not just a preferred pressure setting.
W713 Constant Pressure Pump Controller: Input And Output Options
The following examples are from Liyuan Pump’s 2026 catalog, PDF pages 24–25, printed pages 21–22. Rated output current refers to the drive, not the pump’s measured operating current.
| W713 Model | Catalog Motor Power | Rated Output Current | Catalog Input | Catalog Output |
|---|---|---|---|---|
| W713-2001 | 0.75 kW | 4.5 A | 220 V single-phase | 3-phase, 0–220 V |
| W713-2002 | 1.5 kW | 7 A | 220 V single-phase | 3-phase, 0–220 V |
| W713-2003 | 2.2 kW | 10 A | 220 V single-phase | 3-phase, 0–220 V |
| W713-4010 | 7.5 kW | 18.5 A | 380 V three-phase | 3-phase, 0–380 V |
| W713-4015 | 11 kW | 25 A | 380 V three-phase | 3-phase, 0–380 V |
| W713-4020 | 15 kW | 32 A | 380 V three-phase | 3-phase, 0–380 V |
| W713-4025 | 18.5 kW | 38 A | 380 V three-phase | 3-phase, 0–380 V |
These are selected models, not the complete range. The listed voltage is the catalog nominal value; 0–220 V and 0–380 V describe the drive output range, not a fixed motor voltage at all speeds.
Confirm the latest model data, supply tolerance, overload capacity and motor suitability with the supplier before ordering. The catalog does not establish that every model is suitable for every submersible motor of the same kW.
Can A 220 V Single-Phase Supply Run A Three-Phase Pump?
The catalog lists some W713 models with 220 V single-phase input and 220 V three-phase output. You can consider them for a compatible 220 V three-phase motor after the supplier confirms the drive and motor match.
For example, the catalog lists W713-2002 at 1.5 kW and 7 A output. That does not confirm that every 1.5 kW pump motor is suitable. The supplier must check the motor’s rated current, voltage, frequency, starting requirements and permitted VFD operation.
Two common misunderstandings are important:
- Do not assume a 220 V three-phase output can supply a 380 V-only motor at its rated voltage.
- A drive with single-phase input is not automatically suitable for a single-phase capacitor motor.
If the motor nameplate shows more than one voltage or connection option, ask the motor manufacturer which connection and VFD conditions apply. For more about the supply-side question, see single phase to three phase VFD selection.
Why Does Motor Current Matter As Much As kW?
The controller must supply the motor’s required current within the drive’s applicable ratings and installation conditions. Motor power is useful for an initial shortlist, but it is not the final electrical check.
Suppose a 380 V three-phase motor has a nameplate rating of 11 kW and 27 A. The catalog lists W713-4015 at 11 kW and 25 A output. Even though the power figures match, 27 A exceeds that catalog current rating.
In this hypothetical example, do not approve W713-4015 on the basis of kW alone. Request a selection that accounts for the motor current, overload capability, ambient temperature, cable and applicable derating.
The next catalog model, W713-4020, has a 32 A output rating. That makes it a possible model to assess, not an automatic approval. The drive and motor suppliers still need to confirm compatibility and settings.
How Does The Controller Know When To Change Pump Speed?
A constant-pressure system needs suitable pressure feedback. A pressure sensor measures system pressure and sends a signal to the controller; the controller compares that signal with the desired setpoint and adjusts speed.
A practical quotation should identify:
- The pressure sensor type and measuring range.
- The signal the exact controller configuration accepts.
- Where the installer will place the sensor.
- The desired pressure at that location.
- The required pressure range and protection limits of the system.
A sensor at the pump discharge does not necessarily read the same pressure as a distant outlet. Pipe elevation and friction losses can make the difference important when the end user’s pressure is the real requirement.
Ask the supplier to list the sensor and fittings separately if the quotation does not include them. Do not assume the supplier provides a pressure transmitter merely because the drive supports pressure control.
Can One Constant Pressure Pump Controller Manage Two Pumps?
The W713 catalog lists linkage arrangements including one duty and one standby, master-slave, synchronized operation and big-small pump combinations. It also lists linkage of up to six pumps.
The catalog summary does not specify the exact number of drives, contactors, sensors or control cabinets for every arrangement. A buyer should request a complete system diagram and a written operating sequence.
For a two-pump system, clarify the intended job:
| Requirement | Question To Confirm |
|---|---|
| Duty and standby | Should one pump remain in reserve during normal operation? |
| Duty and assist | Must the second pump run when demand exceeds the first pump’s capacity? |
| Alternating duty | Should the lead pump change to distribute operating time? |
| Fault changeover | What happens if the duty pump or its controller fails? |
A standby pump is not automatically an assist pump. A quotation stating only “two-pump control” does not define the operating logic, the required hardware or how a fault affects water supply.
Is One Drive Enough For Two Pumps?
It depends on the approved control arrangement. “Controls two pumps” can describe different electrical designs; it does not establish that you can connect two motors directly to one output and operate them independently.
Request confirmation of:
- The number and size of drives and pump motors.
- Whether both pumps can run simultaneously.
- Which pump receives variable-speed control.
- The required external contactors, interlocks and protection.
- The approved switching sequence and commissioning procedure.
Do not connect or switch motors on a drive output unless the manufacturer’s design and instructions explicitly permit the arrangement. A qualified control-panel integrator should provide the final electrical design.
Does A Constant Pressure Pump Controller Need A Pressure Tank?
A VFD does not automatically eliminate the need for a pressure tank. A suitable tank can help stabilize pressure and reduce unnecessary starts during very small or intermittent demand.
Tank size, pressure rating and precharge depend on the controller, pump and control settings. Follow the approved system design rather than copying a fixed-size tank from another installation.
If the pump starts and stops frequently during low water demand, investigate the tank, leaks, sensor location and sleep/wake settings. The submersible pump pressure tank article explains the tank-related checks.
What Should You Check For A Deep-Well Submersible Motor?
A borehole pump motor may need different VFD checks from a surface motor. Give the supplier the complete motor-cable length, including the cable from the drive to the wellhead and the down-well section.
Ask both drive and motor suppliers to confirm:
- Minimum and maximum permitted motor frequency.
- Required cooling flow past the motor at reduced speed.
- Motor insulation compatibility with the drive output.
- Whether the installation needs an output reactor, dV/dt filter or sine-wave filter.
- Cable size, grounding and protection settings.
For example, Grundfos’ submersible pump data identifies motor cooling, voltage transients and motor-rated current as considerations for its equipment. Its numerical limits apply to the specified Grundfos products; do not apply them to a Liyuan motor without confirmation.
Submersion alone does not establish that a motor receives enough cooling water when pump speed and flow decrease.
Can A VFD Always Save Energy?
Not necessarily. A VFD can reduce speed when demand permits, but actual savings depend on the pump curve, static lift, pressure requirement, operating hours and control strategy.
A pump that runs near full speed throughout the day may show limited savings compared with an appropriately selected fixed-speed system. Conversely, a system with changing demand may benefit from variable-speed control—but estimate the savings for the actual duty profile.
Avoid selecting a significantly oversized pump solely because a VFD can slow it down. The pump still needs to operate within the manufacturer’s permitted range.
Does The W713 Replace Every Pump Protection Device?
Do not assume so. The catalog lists functions such as auto-sleep and power-on restart, but the supplier must confirm the final protection arrangement for the quoted configuration and installation.
Ask the supplier what the package includes or requires for:
- Motor overload and short-circuit protection.
- Source-water shortage or dry-run conditions.
- Overpressure and sensor failure.
- Supply problems and safe power restoration.
- Emergency stopping and maintenance isolation.
Automatic restart after a power interruption may not be acceptable in every application. Confirm the intended restart behavior and site safety requirements before commissioning.
What Should A W713 Quotation Include?
Send Liyuan Pump the motor nameplate and the following project details:
- Available supply voltage, phase and frequency.
- Pump and motor model, rated kW, voltage and current.
- Required flow and pressure, including where the system must maintain that pressure.
- Number of pumps and whether each is duty, assist or standby.
- Total motor-cable length and installation conditions.
- Water source, expected operating hours and required protection.
- Required pressure sensor, tank, enclosure and communication arrangements.
Request the exact drive models, rated output current, sensor specification, system diagram, component list and commissioning requirements. For a multi-pump system, request the operating and fault-changeover sequence in writing.
Frequently Asked Questions
Can A Constant Pressure Pump Controller Increase Well Yield?
No. It can change pump operation, but it cannot increase the water the well can sustainably supply.
Can I Use A W713-2003 With A 380 V-Only Motor?
The catalog lists W713-2003 with 220 V single-phase input and 0–220 V three-phase output. Do not assume it can supply a 380 V-only motor at rated voltage. Check the motor connection and obtain written supplier confirmation.
Is A Duty-Standby System The Same As Two Pumps Running Together?
No. In duty-standby operation, one pump normally remains in reserve. Running both to meet peak demand is a different duty-assist requirement and needs its own design.
Does The Same kW Guarantee A Correct VFD Match?
No. Compare motor nameplate current with the drive’s applicable output rating and check voltage, phase, motor type, cable, cooling and operating conditions.
Will The Controller Maintain Pressure At Every Tap?
Not necessarily. Pressure at a distant tap also depends on elevation, pipe friction and flow. Agree where the sensor will measure pressure and where users need the minimum pressure.
The best constant pressure pump controller matches the complete water system: supply, motor, pump, sensor, control sequence and operating range.